Model
6618

Tiras-16.128P conventional fire panel: 16 basic zones, expandable to 128. For new projects TIRAS recommends the Tiras PRIME XL.

Discontinued

This model is no longer made. Ask us, and we will suggest a current replacement.

Need installation

Key specifications

Zones
Basic zones: 16, maximum in the system: 128; zone voltage 12 V; zone resistance 250 Ohm
Power supply
220 V, 50 Hz
Dimensions
330 × 410 × 95 mm
Operating temperature
-10 °C – +40 °C
All specifications

Description

The Tiras-16.128P is a conventional fire alarm control panel for large multi-building sites such as warehouses, farms and factories. Its 16 basic zones expand to 128 in the system. TIRAS is discontinuing the model and recommends the Tiras PRIME XL for new projects.

  • RS-485 system bus up to 1000 m, up to 32 devices in the system.
  • Control and programming: up to 4 VPK-16.128 panels; zone and output expansion: up to 14 Tiras-4P, Tiras-8P or Tiras-16P panels.
  • Extinguishing: up to 20 ECD Tiras-1 devices; actuators: up to 8 M-OUT8R modules; ring connection through MKI modules.
  • “Alert”, “Fire” and “Fault” relay outputs plus 2 programmable relays; a log of 1,000 events.
  • microSD card for a configuration backup and firmware updates; Touch Memory; 50 W power supply and an 18 Ah battery.

For servicing an existing system, contact LAGI about fire alarm installation.

Specifications

Alarm system
ZonesBasic zones: 16, maximum in the system: 128; zone voltage 12 V; zone resistance 250 Ohm
Outputs“Alert”, “Fire”, “Fault” relay outputs; 2 programmable relay outputs
InputsUniversal input; external power supply monitoring input
ExpansionSystem bus length: 1000 m; control and programming: VPK-16.128, up to 4; zone and output expansion: Tiras-4P, Tiras-8P, Tiras-16P panels, up to 14; fire extinguishing: ECD Tiras-1, up to 20; actuator control: M-OUT8R, up to 8; RS-485 bus topology and protection: MKI ring interface module, up to 4
Power
Power supply220 V, 50 Hz
Backup batteryLead-acid battery 18 Ah
Power supply unit rating50 W
Physical and environment
Dimensions330 × 410 × 95 mm
Net weight4,2 kg
Ingress protection (IP)IP30
Operating temperature-10 °C – +40 °C

Related products

  • Tiras PRIME XL conventional fire alarm control panel from the Tiras PRIME II series, front view New
    Zones
    Basic zones: 16; maximum in the system: 128; detectors per zone: 32; zone voltage: 24 V
    Communication interfaces
    Ethernet (built in); 2 × RS-485 (line length up to 1000 m); USB-C; GSM (with the M-2G module); 4G (M-LTE module)
    Power supply
    Main power supply: 220 V, 50 Hz; 2 monitored 24 V power outputs

    Price on request