Skip to content
TIRAS

Tiras PRIME A addressable fire alarm control panel

Model
6500

Tiras PRIME A addressable fire panel: 2 built-in addressable interfaces with up to 250 devices each, and up to 128 interfaces in the system.

On order

Price on request

Send a request. A manager will name the price and the delivery time during working hours.

Key specifications

Communication interfaces
Ethernet; 2 × SPE; USB-C; M-LTE or M-2G communicator (installed on the panel board)
Power supply
Main power supply: 220 V, 50 Hz; 2 controlled 24 V power outputs
Dimensions
350 × 365 × 100 mm
Operating temperature
-10 °C – +40 °C
All specifications

Description

The Tiras PRIME A is an addressable fire alarm control panel for buildings where you need to know exactly which detector went off and in which room. Every addressable device has its own address, so the location of an alarm or a fault shows on the panel without walking the floors.

  • 2 built-in addressable interfaces, up to 128 in the system; up to 250 devices in a loop and up to 32 on a radial line.
  • Loop or radial topology, line length up to 2000 m, branches from any device.
  • 6 built-in outputs, including 2 programmable transistor outputs and 2 relays for sirens; up to 1,000 outputs in the system.
  • Ethernet, 2 SPE interfaces and USB-C; an M-LTE or M-2G communicator fits on the board for reporting to a monitoring station.
  • Built-in 50 W power supply and room for 2 lead-acid or LiFePO4 batteries of 7–9 Ah.

The HW2 version adds 2 relay outputs and USB Type-C. LAGI designs and commissions the system as part of fire alarm installation.

Specifications

Alarm system
Addressable interfacesBasic: 2, maximum in the system: 128; Topology: loop or radial; Addressable devices: up to 250 in a loop, up to 32 on a radial line; Interface voltage: 24 V; Interface resistance: 125 Ohm; Length: up to 2000 m; Radial branches: from any device
OutputsBasic: 6, maximum in the system: 1000; “Fire”, “Fault”; 2 programmable transistor outputs for connecting sirens; 2 programmable relays for connecting sirens
InputsBasic: 2, maximum in the system: 1000; 2 for connecting open collector or dry contact outputs
Communication
Communication interfacesEthernet; 2 × SPE; USB-C; M-LTE or M-2G communicator (installed on the panel board)
Power
Power supplyMain power supply: 220 V, 50 Hz; 2 controlled 24 V power outputs
Backup battery2 lead-acid or LiFePO4 batteries 7-9 Ah
Power supply unit rating50 W
Output current1 A
Physical and environment
Dimensions350 × 365 × 100 mm
Net weightWeight (without battery): 3 kg
Ingress protection (IP)IP30
Operating temperature-10 °C – +40 °C

Need it installed?

LAGI will deliver, install and set up the equipment and provide warranty service afterwards.