TIRAS
Tiras PRIME S conventional fire alarm control panel
- Model
- 6611
Tiras PRIME S conventional fire panel: 4 zones with up to 32 detectors each, and up to 4 expansion devices over RS-485.
On order
Price on request
Send a request. A manager will name the price and the delivery time during working hours.
Key specifications
- Zones
- Basic zones: 4; detectors per zone: 32; zone voltage: 24 V
- Communication interfaces
- RS-485 (bus length up to 1000 m); USB-C; GSM (with the M-2G module); 4G (M-LTE module); Wi-Fi (M-WiFi module); Ethernet (M-NET+ module)
- Power supply
- Main power supply: 220 V, 50 Hz; 2 monitored 24 V power outputs
- Dimensions
- 280 × 280 × 80 mm
- Operating temperature
- -5 °C – +40 °C
Description
The Tiras PRIME S is a conventional fire alarm control panel from the Tiras PRIME II series for the smallest sites such as shops, pharmacies and cafés. Zones run at 24 V, so a thinner cable can be used.
- 4 zones, up to 32 detectors in each.
- Up to 4 expansion devices over RS-485: up to 2 M-OUT8R or M-OUT2R box modules and up to 2 ECD Tiras 1X extinguishing control devices.
- 2 universal slots for communicators (M-2G or M-LTE plus M-WiFi or M-NET+ at the same time) or an M-OUT2R relay module; 2 built-in relays for alarms or automation.
- DETECTO PLUS mode with DETECTO 10 series detectors: the panel receives a signal when a smoke chamber is dirty or a heat sensor fails, and no end-of-line resistor is needed in the zone.
- Built-in 35 W power supply with surge protection and a selectable charging current; one lead-acid or LiFePO4 battery of 7–8 Ah.
Enclosure 280 × 280 × 80 mm, 1.25 kg without the battery. LAGI designs and installs the system as part of fire alarm installation.
Specifications
| Zones | Basic zones: 4; detectors per zone: 32; zone voltage: 24 V |
|---|---|
| Outputs | “Fire”, “Fault”; 2 relay outputs for alarm notification or automation control |
| Expansion | Up to 4 devices in total; up to 2 M-OUT8R or M-OUT2R box; up to 2 ECD Tiras 1X |
| Communication interfaces | RS-485 (bus length up to 1000 m); USB-C; GSM (with the M-2G module); 4G (M-LTE module); Wi-Fi (M-WiFi module); Ethernet (M-NET+ module) |
|---|
| Power supply | Main power supply: 220 V, 50 Hz; 2 monitored 24 V power outputs |
|---|---|
| Backup battery | Lead-acid or LiFePO4 battery 7–8 Ah |
| Power supply unit rating | 35 W |
| Output current | 800 mA (2 outputs of 400 mA each) |
| Dimensions | 280 × 280 × 80 mm |
|---|---|
| Net weight | Weight (without battery): 1.25 kg |
| Ingress protection (IP) | IP30 |
| Operating temperature | -5 °C – +40 °C |
Need it installed?