Skip to content
FYB

FYB FY-200E voice evacuation and fire alarm panel

Model
FY-200E
SKU
FYB-88442

Voice evacuation unit: on a fire alarm signal, a siren or a pre-recorded voice message is sent to the PA system.

On order

Price on request

Send a request. A manager will name the price and the delivery time during working hours.

Key specifications

Dimensions
484(W)×350(D)×88(H)mm
Frequency response
100Hz-3.4kHz(±3dB)
Power supply
AC 220-240V/50-60Hz
All specifications

Description

The FYB FY-200E is a voice evacuation panel for fire alarms. On a signal from the fire alarm system, a recorded voice message or a siren is sent to the PA system automatically.

  • Alarm input and output on jack sockets; the input triggers on a contact closure (0 V).
  • Built-in recorder: a message of up to 60 s stored on a memory chip, more than 8000 rewrites; recording from an external microphone or line; start, stop and play functions.
  • Mode selector: siren, play, record, off.
  • Protected volume controls for recording and alarm output.
  • Fire, start, stop and power indicators.
  • Jack inputs: microphone (5 mV, 600 Ω) and line (400 mV, 10 kΩ); output from 200 mV, 100 Hz – 3.4 kHz response.

The output is line level, for a PA amplifier. 220–240 V mains, 484 × 350 × 88 mm, 6.1 kg. The link to the fire alarm and the wording of the message are planned when audio and public address systems are designed.

Specifications

Access control
Alarm inputOne alarm input, 0V short circuit closed contact
Hardware
Voice recorderIC inside, 60 seconds, write in more than 8,000 times.
Power
Power supplyAC 220-240V/50-60Hz
Audio
Frequency response100Hz-3.4kHz(±3dB)
InputsMicrophone: <5mV, 600Ω, unbalanced; ; Line: <400mV 10kΩ, unbalanced
Outputs>200mV Sire or Recorded Message
Physical and environment
Net weight6.1kg
Gross weight7.8kg
Dimensions484(W)×350(D)×88(H)mm
Package dimensions520(W)×435(D)×185(H)mm

FAQ

What is 100V constant voltage system and why is it needed?

100V constant voltage system is special audio technology using high voltage (100V) and low current for signal transmission. This allows: 1) connect dozens of speakers to one amplifier (50-100+ speakers), 2) use thin cables (0.75mm²-1.5mm²) over long distances (300-1000m), 3) minimal signal loss, 4) individual power adjustment of each speaker via transformer. Ideal for large facilities.

How many speakers can be connected to one amplifier?

Depends on amplifier power and speaker power. Formula: quantity = amplifier power ÷ speaker power. Example: 240W amplifier + 6W speakers = 40 speakers (240÷6=40). 500W amplifier + 10W speakers = 50 speakers. Always leave 20% reserve and consider zone distribution.

Can PA system integrate with fire alarm?

Yes, PA system must integrate with fire alarm for voice evacuation (EN54-16 standard). When fire panel activates, PA system automatically: 1) stops background music, 2) plays pre-recorded evacuation message in all zones, 3) turns all speakers to maximum volume, 4) continues message until fire panel is reset. This is life-safety critical function.