FYB FY-200E voice evacuation and fire alarm panel
- Model
- FY-200E
- SKU
- FYB-88442
Voice evacuation unit: on a fire alarm signal, a siren or a pre-recorded voice message is sent to the PA system.
On order
Price on request
Send a request. A manager will name the price and the delivery time during working hours.
Key specifications
- Dimensions
- 484(W)×350(D)×88(H)mm
- Frequency response
- 100Hz-3.4kHz(±3dB)
- Power supply
- AC 220-240V/50-60Hz
Description
The FYB FY-200E is a voice evacuation panel for fire alarms. On a signal from the fire alarm system, a recorded voice message or a siren is sent to the PA system automatically.
- Alarm input and output on jack sockets; the input triggers on a contact closure (0 V).
- Built-in recorder: a message of up to 60 s stored on a memory chip, more than 8000 rewrites; recording from an external microphone or line; start, stop and play functions.
- Mode selector: siren, play, record, off.
- Protected volume controls for recording and alarm output.
- Fire, start, stop and power indicators.
- Jack inputs: microphone (5 mV, 600 Ω) and line (400 mV, 10 kΩ); output from 200 mV, 100 Hz – 3.4 kHz response.
The output is line level, for a PA amplifier. 220–240 V mains, 484 × 350 × 88 mm, 6.1 kg. The link to the fire alarm and the wording of the message are planned when audio and public address systems are designed.
Specifications
| Alarm input | One alarm input, 0V short circuit closed contact |
|---|
| Voice recorder | IC inside, 60 seconds, write in more than 8,000 times. |
|---|
| Power supply | AC 220-240V/50-60Hz |
|---|
| Frequency response | 100Hz-3.4kHz(±3dB) |
|---|---|
| Inputs | Microphone: <5mV, 600Ω, unbalanced; ; Line: <400mV 10kΩ, unbalanced |
| Outputs | >200mV Sire or Recorded Message |
| Net weight | 6.1kg |
|---|---|
| Gross weight | 7.8kg |
| Dimensions | 484(W)×350(D)×88(H)mm |
| Package dimensions | 520(W)×435(D)×185(H)mm |
FAQ
What is 100V constant voltage system and why is it needed?
100V constant voltage system is special audio technology using high voltage (100V) and low current for signal transmission. This allows: 1) connect dozens of speakers to one amplifier (50-100+ speakers), 2) use thin cables (0.75mm²-1.5mm²) over long distances (300-1000m), 3) minimal signal loss, 4) individual power adjustment of each speaker via transformer. Ideal for large facilities.
How many speakers can be connected to one amplifier?
Depends on amplifier power and speaker power. Formula: quantity = amplifier power ÷ speaker power. Example: 240W amplifier + 6W speakers = 40 speakers (240÷6=40). 500W amplifier + 10W speakers = 50 speakers. Always leave 20% reserve and consider zone distribution.
Can PA system integrate with fire alarm?
Yes, PA system must integrate with fire alarm for voice evacuation (EN54-16 standard). When fire panel activates, PA system automatically: 1) stops background music, 2) plays pre-recorded evacuation message in all zones, 3) turns all speakers to maximum volume, 4) continues message until fire panel is reset. This is life-safety critical function.
Need it installed?
LAGI will deliver, install and set up the equipment and provide warranty service afterwards.