Heiman HM-203 wired heat detector

Model
9693

Wired heat detector for a fire alarm control panel: alarm when the temperature climbs faster than 8 °C per minute, 9–35 V DC supply.

On order

Price on request

Send a request. A manager will name the price and the delivery time during working hours.

Key specifications

Alarm threshold
Rate-of-rise alarm: temperature rising rate>8 °C/M
Power supply
DC9 V-35 V
Dimensions
Φ100 × 48 mm
All specifications

Description

The Heiman HM-203 is a wired heat detector for a fire alarm system built around a control panel. Detection is rate-of-rise: the alarm goes off when the temperature climbs faster than 8 °C per minute.

With the rate-of-rise principle, the rapid heating of a fire triggers the alarm, while a slow rise in temperature during the day or from heating does not.

  • 9–35 V DC supply; standby current up to 50 µA, alarm current 35 mA at 12 V and 83 mA at 24 V.
  • 2-wire or 4-wire connection.
  • Output for a remote LED indicator, so an alarm can be seen from outside the room.
  • Ceiling mounting, Φ100 × 48 mm housing.
  • Works from -10 to 50 °C at up to 95 % humidity.

Detectors connect to the control panel loop; LAGI lays out the loops and positions under fire alarm installation.

Specifications

General
Alarm thresholdRate-of-rise alarm: temperature rising rate>8 °C/M
Access control
Alarm outputRemote LED Indicator
Power
Power supplyDC9 V-35 V
Standby current≤50uA
Alarm current35 mA (12 V); 83 mA (24 V)
Physical and environment
DimensionsΦ100 × 48 mm
MountingCeiling mounted
Wiring2 wire, 4 wire
Operating environment-10 °C – +50 °C, Humidity≤95%RH

FAQ

What's the difference between conventional and addressable fire systems?

Conventional systems – detectors grouped into zones (e.g. "Zone 3 - 3rd floor"), panel shows only zone, not exact detector, 4-wire cabling (2 wire power + 2 wire signal), cheaper, simple installation, ideal for small/medium buildings (4-32 zones). Addressable systems – each detector has unique ID, panel shows exact detector (e.g. "Detector #47"), 2-wire Loop cabling, more expensive, complex programming, ideal for large buildings (128-512 addresses). Recommendation: conventional – small offices, shops, residential houses. Addressable – hotels, hospitals, shopping centers.

What is zone in conventional fire system?

Zone is group of detectors representing specific area in building. How it works: all detectors in one zone connect to one 4-wire cable that goes to zone terminal on panel. When any detector in this zone triggers, panel shows "Zone 3 alarm", but doesn't know which specific detector. Zone planning: 1) geographical – one zone = one floor or one wing. 2) functional – one zone = one type of space (e.g. all bedrooms). 3) size – one zone maximum 20-30 detectors, maximum 2000m² area. Example: 3-floor building → Zone 1 (1st floor), Zone 2 (2nd floor), Zone 3 (3rd floor), Zone 4 (basement).

What is EOL (End-of-Line) resistor and why is it needed?

EOL (End-of-Line) resistor is small resistor (usually 4.7kΩ or 10kΩ) installed in last detector of zone in conventional fire systems. Why needed: EOL resistor allows panel to monitor zone cable integrity. How it works: panel sends small current into zone cable and measures resistance. 1) normal state – panel sees EOL resistor → zone OK. 2) fire – detector closes contact → resistance changes → panel shows "Zone 3 alarm". 3) cable break – EOL resistor not visible → panel shows "Zone 3 fault". 4) short-circuit – resistance very low → panel shows "Zone 3 short-circuit". This ensures system always works and is not damaged.

Need it installed?