Heiman HM-920 alarm control panel

Model
9692

Control panel for a conventional fire alarm with 2 or 4 zones: audible and visual alarm on the panel, relay output, backup batteries.

On order

Price on request

Send a request. A manager will name the price and the delivery time during working hours.

Key specifications

Power supply
AC220 V±15%/50 Hz
Dimensions
300 × 210 × 100 mm
Zones
2 zones / 4 zones
All specifications

Description

The Heiman HM-920 is an alarm control panel for a conventional fire alarm system. Smoke and heat detectors connect to the panel over 2-wire loops, and alarms are shown by zone: 2 or 4 zones, depending on the version.

In a conventional system an alarm comes from a whole zone (loop) rather than from a numbered detector, so a building is split into zones that make the source of a fire quick to find.

  • Alarm: audible and visual signal on the panel, plus a relay output for external devices.
  • Supply AC 220 V ±15 %, 50 Hz; backup from two 12 V, 2.6 Ah batteries.
  • Current at 24 V: under 120 mA on standby, under 180 mA in alarm.
  • Wall mounting, 300 × 210 × 100 mm housing.
  • Works from -10 to 60 °C at 5–95 % humidity.

Splitting the building into zones and sizing the loops are part of fire alarm installation.

Specifications

Access control
Alarm outputAudio & flash alarm; Relay output
Power
Power supplyAC220 V±15%/50 Hz
Backup batteryDC12 V/2.6Ahx2
Standby current<120 mA@24 V
Alarm current<180 mA@24 V
Audio
Zones2 zones / 4 zones
Physical and environment
Dimensions300 × 210 × 100 mm
MountingWall mounted
Wiring2 wire
Operating environment-10 °C – 60 °C (5% – 95%RH)

FAQ

What's the difference between conventional and addressable fire systems?

Conventional systems – detectors grouped into zones (e.g. "Zone 3 - 3rd floor"), panel shows only zone, not exact detector, 4-wire cabling (2 wire power + 2 wire signal), cheaper, simple installation, ideal for small/medium buildings (4-32 zones). Addressable systems – each detector has unique ID, panel shows exact detector (e.g. "Detector #47"), 2-wire Loop cabling, more expensive, complex programming, ideal for large buildings (128-512 addresses). Recommendation: conventional – small offices, shops, residential houses. Addressable – hotels, hospitals, shopping centers.

What is zone in conventional fire system?

Zone is group of detectors representing specific area in building. How it works: all detectors in one zone connect to one 4-wire cable that goes to zone terminal on panel. When any detector in this zone triggers, panel shows "Zone 3 alarm", but doesn't know which specific detector. Zone planning: 1) geographical – one zone = one floor or one wing. 2) functional – one zone = one type of space (e.g. all bedrooms). 3) size – one zone maximum 20-30 detectors, maximum 2000m² area. Example: 3-floor building → Zone 1 (1st floor), Zone 2 (2nd floor), Zone 3 (3rd floor), Zone 4 (basement).

What is EOL (End-of-Line) resistor and why is it needed?

EOL (End-of-Line) resistor is small resistor (usually 4.7kΩ or 10kΩ) installed in last detector of zone in conventional fire systems. Why needed: EOL resistor allows panel to monitor zone cable integrity. How it works: panel sends small current into zone cable and measures resistance. 1) normal state – panel sees EOL resistor → zone OK. 2) fire – detector closes contact → resistance changes → panel shows "Zone 3 alarm". 3) cable break – EOL resistor not visible → panel shows "Zone 3 fault". 4) short-circuit – resistance very low → panel shows "Zone 3 short-circuit". This ensures system always works and is not damaged.

Need it installed?